MST200-Standard Panel Mounted Flow Controller

The purpose of flow controller working with flow sensor is to measure the flow rate and to record the total flow of media like liquids, gases or loose materials. A wide range of total flow indication (up to 16 digits) allows controlling the flow rate for a long operation time. Thanks to the built-in batcher function the MST200 can be used in many industries like: food pharmaceutical or paint and varnish industry. The REL/0C control outputs can be programmed depending on the flow rate, total flow or batcher. Additionally the controller may be equipped with analogue outputs, according to the customer selection: active current output ( 0/4 ...20mA ) , passive isolated current output ( 4 ... 20mA ) or active voltage output ( 0/1 ..5V,0/2...10V ) . The controller can be configured with the local keyboard or free S-Config software via the RS-485 communication port.
Applications

Working with FTB/FGR series

Introduction

  1. 6-digit LED display

  2. Flow meter/totalizer/batcher

  3. Flow rate/total flow display

  4. 1 pulse counting input + 3 control inputs

  5. RS-485 / Modbus RTU

  6. Free configuration software S-Config

Technical

Specification Table

Order No

Supply voltage19...50Vdc,16...35Vac or 85...260Vac/Vdc
Power consumptionMax. 6.5VA
AccuracyFrequency:±0.02%(over full temperature range); flow rate: depends on sensor accuracy
ShowRed LED,high6x13mm
Display value range0...999999 +decimal point
Reading Accuracy
Instantaneous flowChoose0.0.00000unit
Cumulative Flow and BatchingChoose0.0.000unit
Input (pulse, fully isolated)
Eliminate jitter and controllable pulse width counting input, input frequencyMax. 10.0 kHz;
Batch processing clearing: valid edge or valid level;
Cumulative reset: valid edge or valid level; measurement lock: valid edge or valid level
Input level (12mA@24V)Low level:0...1V;High level:10...30V(about12mA @ 24V)
Metering capacity
AccumulationMore than the4x109m3 (max. 16effective number)
Batch processingGundam 65536m3
Display unit
Instantaneous flow L orm3 /seconds, minutes, hours
Cumulatives and batches L orm3
Pulse wait width0.1.39.9seconds can be set
Output type
Switch output2x REL ,Imax =1A,Umax =30Vdc/250Vac
No isolated voltage output0/1...5V, 0/2...10V (max. 0...11V);RA≥2KΩ
resolution13 bits
Communication InterfaceRS-485,8N1and8N2,1200...115200 bit/s;
Modbus RTU(without galvanic isolation)
Operating temperature0...+50°C
Degree of protectionIP65(Add protective film to the display panel);IP40(standard);IP20(Housing and connection clip)
Meter size (longxWidthxhigh)96x48x100mm